Double EOL zone balancing: wiring and how the panel reads it
18 October 2026 · updated 28 October 2026 · Theo
FRLire cette fiche en françaisDouble EOL balancing carries two pieces of information on a single pair of wires: the state of a detector's alarm contact and that of its tamper.
The panel no longer reads a contact as open or closed: it measures a resistance. Normal, alarm, cover open, cable cut or shorted each give a different value. That is how it tells an intrusion from tampering with the line.
Wiring, simulator, readings, values per panel and field mistakes: it is all below.
- No resistor: a link wire passes for normal.
- Single EOL: the link wire is seen, but a cut looks the same as an alarm.
- Double EOL:
R1in series,R2in parallel across the alarm contact, tamper in series. - Readings: normal =
R1, alarm =R1 + R2, cover open or cable cut = infinite, short circuit = 0 Ω. - Resistors: in the detector, never at the panel terminals.
Wiring a detector
R1 and the alarm contact.R2. At rest, the closed contact shorts it out: the current only goes through R1. With the contact open, it goes through R2 and the resistance read goes up.Zone simulator
A zone wired with double EOL. The buttons open the alarm contact or the cover, cut the cable or short it. The resistance read and the zone state are shown live.
Normal: the current goes through the tamper, R1 and the closed alarm contact, which shorts out R2. The panel reads R1.
The panel's four readings
| Situation | Reading |
|---|---|
| Alarm contact closed, cover closed | R1: normal |
| Alarm contact open, cover closed | R1 + R2: alarm |
| Cover open or cable cut | Infinite: tamper |
| Cable shorted | 0 Ω: tamper or fault depending on the panel |
- Tolerance ranges: the panel compares the measurement with a range around each expected value.
- SPC example with 1 kΩ + 1 kΩ: normal from 700 Ω to 1.3 kΩ, alarm from 1.5 to 2.6 kΩ, short circuit below 300 Ω, disconnected outside the ranges.
- Cover open: the loop is cut whatever the alarm contact does. Tamper always takes priority.
Why balance a zone
A simple closed loop only knows closed or open: a link wire between the two wires defeats it without the panel noticing.
With an end-of-line resistor (single EOL), the panel expects a value: the link wire (0 Ω) and the cut (infinite) are detected. Double EOL adds a second resistor to encode the alarm contact. The tamper travels on the same pair: one conductor fewer per detector, one terminal fewer on the panel.
For a zone with an NC contact, this is what the panel reads.
| Mode | Readings |
|---|---|
| No end of line | Normal 0 Ω, alarm infinite. Cut cable read as an alarm, short circuit as normal. |
| Single EOL | Normal R, alarm infinite. Cut cable read as an alarm, short circuit (0 Ω) detected. |
| Double EOL | Normal R1, alarm R1 + R2. Cut cable (infinite) as tamper, short circuit (0 Ω) detected. |
- Single EOL: resistor in series with the contact, in the detector. On SPC with 1 kΩ: normal from 700 Ω to 1.3 kΩ, alarm above 23 kΩ, short circuit below 300 Ω. On TIL, this mode is called NFS.
- Three resistors: on TIL, the EQUI6 mode reads alarm and tamper separately. SPC and Galaxy offer it for detectors that also report a fault or masking.
NC and NO contacts
- NC (normally closed, “NF” in French): passes current at rest, opens when the detector triggers or the door opens.
- NO (normally open): the opposite, open at rest, closed in alarm.
- Setting: the panel must know which one it is supervising. On RISCO Agility 3 or TIL, for example, it is set input by input.
- Never mixed in series: an NO contact leaves the loop open at rest, and the zone stays in alarm permanently.
Values and settings per panel
The values depend on the panel and its programming. The most common ones:
| Panel | R1 / R2 |
|---|---|
| Honeywell Galaxy | 1 kΩ / 1 kΩ: normal 1 kΩ, alarm 2 kΩ |
| Vanderbilt SPC (default) | 4.7 kΩ / 4.7 kΩ: normal 4.7 kΩ, alarm 9.4 kΩ |
| TIL TILLYS and modules (EQUI mode) | 1 kΩ / 1 kΩ: normal 1 kΩ, alarm 2 kΩ |
| RISCO Agility 3 (DEOL mode) | 10 kΩ / 10 kΩ |
On SPC, other combinations are chosen in the zone configuration. Before wiring, check the combination active on the panel or the expansion module.
Where the mode and values are set (labels as they appear on panels set to French):
- SPC: “Fin de ligne” (end of line) parameter of each input, or for all zones in the options.
- Galaxy Dimension: parameter 51.46, resistor selection (1 kΩ balanced loop by default, 1 % resistors).
- TIL: Matériel > Configuration Entrées / Sorties (hardware, inputs/outputs configuration), “Inputs” tab. All inputs in EQUI by default since version 5.9.
- RISCO Agility 3: “Câblage” (wiring) parameter of the input (NO by default, NC or DEOL).
Several contacts on one zone
If the specification allows it: alarm contacts in series with a single R2 in parallel across the whole, tampers in series with a single R1 for the whole loop. The panel will not know which contact triggered.
R1 + 2 × R2. On SPC with 4.7 kΩ + 4.7 kΩ, that makes 14.1 kΩ, beyond the alarm range which stops at 11.9 kΩ: the panel sees a disconnection. Galaxy, on the other hand, provides for this wiring: 1 kΩ per detector, up to ten detectors per zone.Checking a zone with a multimeter
R1, plus a few ohms of cable.R1 + R2.A value that is close but off often points to a resistor of the wrong value or a badly placed jumper. The colour bands can be read at a glance:
- 1 kΩ: brown, black, red.
- 2.2 kΩ: red, red, red.
- 4.7 kΩ: yellow, violet, red.
Guides by device
Wiring a specific device with double EOL:
- Detection Motion detector Motion detector: diagram, zone states and resistor values.
- Perimeter detection Optex SL-200QDM infrared beam Power, alarm and tamper with 1k/1k double EOL.
- Door / window Magnetic door contact Reed switch closed at rest and tamper contact, two 1 kΩ resistors.
- Door / window Door contacts in series Several door contacts on one panel zone.
- Door / window 2-wire door contact or floor contact Alarm pair only, no tamper pair.
- Door / window Floor contact or door contact with a junction box 4-wire contact connected through a junction box.
- Door / window Two door contacts or floor contacts, one junction box Double door or gate: two contacts on a single junction box and a single zone.
Common pitfalls
R1: the zone stays in fault. Alarm still gives R1 + R2, which can be misleading during tests.R2 and masks the alarm. Always in series.Sources: SPC 3.11, wiring the zone inputs (in French) · TILLYS CUBE, TILLYS NG and remote modules register list (GR-10005-FR, in French), § 3.2 · Galaxy Dimension installation manual (Honeywell), zone wiring · Agility 3 installation manual (RISCO), input wiring.