Wiring door contacts in series with double EOL

17 July 2026 · updated 25 October 2026 · Theo

FRLire cette fiche en français
Câblage DO en série
Click to enlarge
●○
Difficulty: Intermediate
⏱️
Reading time: ~4 min

Wiring in series connects several door contacts (DO, from the French “détecteur d’ouverture”) to one and the same zone of the control panel. The contacts form a loop: as long as every door and window is closed, the loop is in its normal state. As soon as a single contact opens, the loop is broken and the zone goes into alarm.

This arrangement comes with double EOL supervision (two end-of-line resistors), which lets the panel tell normal, alarm, open circuit and short circuit apart on a single pair of wires. The principle, the ranges used by each panel and their settings are covered in the guide Double EOL zone balancing.

⚡
Key points
  • Several door contacts on one zone → contacts wired in series (loop).
  • A single opening is enough to put the zone into alarm.
  • Double EOL supervision: 1 kΩ in normal state, 2 kΩ in alarm.
  • Both 1 kΩ resistors go on the last contact of the loop.

How series wiring works

The contacts are connected one after the other on the same Zone / Common pair coming from the panel. The first contact receives the zone, continues to the next contact, and so on up to the last contact, which carries the end-of-line resistors.

The benefit: several doors or windows are protected while using a single zone input. The trade-off: the panel cannot tell which contact was opened, since the whole loop is seen as one zone.

!
No identification possible
All the contacts of one loop share a single zone: on an alarm, the panel reports the zone, not the specific contact that opened.

Other ways of wiring several contacts on one zone, depending on the panel, are described in the guide Double EOL zone balancing.

Wiring diagram

Wiring diagram of two door contacts in series on one zone: Zone and Common from the panel to the first contact, loop continued to the second, which carries both 1 kΩ resistors. Normal 1 kΩ, alarm 2 kΩ.

Click to enlarge

Reading the zone

The double end-of-line resistor gives the panel four distinct states from a single loop:

Resistance seen by the zone State
1 kΩ Normal: loop closed
2 kΩ Alarm: one contact open
0 Ω (short circuit) Tamper or fault, depending on the panel: line shorted
∞ (open circuit) Tamper: line cut
!
Where the resistors go
Both 1 kΩ resistors always go on the last contact of the loop, not at the panel. Fitted at the panel end, the line supervision no longer detects a cut cable between the contacts.

Sources: Galaxy Dimension installation manual (Honeywell), zone wiring · TILLYS CUBE, TILLYS NG and remote modules register list (GR-10005-FR, in French), § 3.2.

DO: door contact
Magnetic contact fitted on a door or window. Its contact opens as soon as the protected door or window opens.
EOL: End Of Line
End-of-line resistor that supervises the loop. With double EOL, two resistors let the panel tell normal, alarm, open circuit and short circuit apart.