16 April 2026 · updated 28 October 2026 · Theo

FRLire cette fiche en français
Câblage volumétrique en double résistance - 2eol
Click to enlarge
●○
Difficulty: Intermediate
⏱️
Reading time: ~4 min

Double EOL (double End of Line) lets the panel supervise the line of a motion detector permanently, and tell normal, alarm, tamper and short circuit apart on a single pair of wires.

The principle, the ranges used by each panel and their settings are covered in the guide Double EOL zone balancing. This guide details the connection of the detector itself.

⚡
The essentials in 30 seconds
  • Two resistors in the zone loop: R2 in parallel across the NC alarm contact, R1 in series with the tamper contact.
  • With 1 kΩ + 1 kΩ (Galaxy Dimension default, EQUI mode on TIL panels): normal 1 kΩ, alarm 2 kΩ, tamper or cut ∞, short circuit 0 Ω.
  • Resistors at the detector, never in the panel.
  • The values fitted must match the zone setting on the panel.

Motion detector terminals

Names vary between manufacturers, but the pinout is the same in the vast majority of cases:

Terminal Function (other names)
+12V / VCCPositive supply (12 V DC). Also: AUX+, PWR, +
GND / 0VSupply ground. Also: AUX−, COM, −
NCNC contact: alarm output, opens when there is movement. Also: OUT, AL, C/NC
TAMPERNC contact: tamper, opens if the housing is opened. Also: T, AUX, TAMP

Wiring procedure

Wiring diagram of a motion detector with double EOL: terminal block minus, plus, NC, NC, T, T; +12 V and 0 V supply, Zone and Com wires to the panel, R2 in parallel across the NC contact and R1 in series with the tamper

Click to enlarge

1
Identification
Find the +12V, GND, NC alarme (NC alarm) and TAMPER terminals on the detector: check the manual for the model.
2
Power
Connect +12V and GND from the panel's auxiliary supply or a remote power supply.
3
Fitting R2
Fit R2 in parallel across the NC alarm contact, between the two NC terminals of the detector.
4
Fitting R1
Fit R1 in series between the second NC terminal and the first T terminal (tamper).
5
Zone wiring
Connect the zone wire to the first NC terminal and the common to the second T terminal: panel → NC alarm + R2 → R1 → tamper → back to panel.
6
Ohmmeter check
Before powering up, measure from the panel: the value of R1 in normal state (~1 kΩ with 1 kΩ + 1 kΩ). Check that there is no short circuit (0 Ω) or cut (∞).
7
Panel setup
Set the zone to double EOL with the values of the resistors fitted: see the settings for each panel.

Simulator

The simulator reproduces this wiring. The buttons simulate movement, opening the cover, cutting or shorting the cable: the resistance read and the zone state are shown live.

Resistors R1 + R2
Resistance read1 kΩ
Zone stateNormal

Normal: the current goes through the tamper, R1 and the closed alarm contact, which shorts out R2. The panel reads R1.

Motion detector with double EOL: panel, cable and detector with NC alarm contact, tamper, end-of-line resistor R1 and alarm resistor R2 Panel 1 kΩ Z1 0V Motion detector Cable AP R1 1 kΩ NC R21 kΩ
Measuring current Wire with no current Cut or short circuit R1: end-of-line resistor, in series in the loop. R2: alarm resistor, in parallel across the NC contact. AP: tamper contact (“autoprotection”), in series.

Table of zone states

For 1 kΩ + 1 kΩ resistors:

State Contacts: measured resistance
NormalAlarm and tamper closed: R1 = 1 kΩ
AlarmAlarm open, tamper closed: R1 + R2 = 2 kΩ
Tamper / CutTamper open, alarm either way: ∞ (open circuit)
Short circuit0 Ω

With 4.7 kΩ + 4.7 kΩ (default on SPC panels), the values become 4.7 kΩ (normal) and 9.4 kΩ (alarm). The logic is the same.

Points to watch

!
Where the resistors go
Fit the resistors at the detector, never in the panel: otherwise line supervision is only partial.
!
Values set by the panel
Stick strictly to the values required by the panel: any difference leads to permanent zone faults.
!
Several detectors on one zone
The wiring depends on the panel: see Several contacts on one zone in the Double EOL zone balancing guide.

FAQ

My detector has no tamper terminal: what do I do?

Without a tamper contact, a true double EOL with tamper supervision is not possible. The wiring stays the same without the tamper contact: R2 in parallel across the NC alarm contact, R1 in series. The panel will detect cuts and short circuits, but not the opening of the housing (see the guide 2-wire door contact or floor contact). Prefer detectors with a tamper for any professional installation.

Sources: Galaxy Dimension installation manual (Honeywell), zone wiring · TILLYS CUBE, TILLYS NG and remote modules register list (GR-10005-FR, in French), § 3.2 · SPC 3.11, wiring the zone inputs (in French).