6 April 2026 · updated 25 October 2026 · Theo
FRLire cette fiche en français
A floor-mounted contact (“sabot”) or a door contact (DO) usually has 4 wires: one pair for the alarm circuit and one pair for the cable tamper.
When the cable goes through a junction box (BR on the diagram), the double EOL resistors are fitted in the junction box, which makes wiring and on-site diagnosis easier.
The panel then reads R1 in normal state and R1 + R2 in alarm. The principle, the ranges used by each panel and their settings are covered in the guide Double EOL zone balancing.
- 4-wire floor contact or door contact: one alarm pair, one tamper pair.
- Double EOL with 2 ×
1 kΩ, fitted in the junction box. - Ohmmeter on the alarm pair:
≈ 1 kΩin normal state,≈ 2 kΩin alarm,∞ Ωif the cable is cut. Tamper pair:0 Ω. - Never put R1 and R2 in series: the panel would not recognise the zone.
What you need
| Item | Specification |
|---|---|
| Contact type | Floor contact or door contact, 4 wires |
| Zone type | Double EOL through a junction box |
| EOL resistors | 2 × 1 kΩ |
| Junction box | Standard junction box |
| Compatible with | Galaxy GD-48 / GD-96 / GD-264 / GD-520 / TIL panel |
| Power supply | Passive: no power required |
Ohmmeter reference values
| State | Measured value |
|---|---|
| Contact closed (normal) | ≈ 1 kΩ |
| Contact open (alarm) | ≈ 2 kΩ |
| Cable cut (tampering) | ∞ Ω (open circuit) |
| Tamper | 0 Ω (continuity) |
Identifying the wires
| Wires (in our example) | Role |
|---|---|
| Yellow + White | “Alarm” pair: EOL circuit |
| Brown + Blue | “Tamper” pair: continuity |
- Closed ≈ 1 kΩ / open ≈ 2 kΩ: this is the alarm pair.
- Continuity (0 Ω): this is the tamper pair.
Wiring in the junction box
In the junction box, R2 is wired across the two wires of the alarm pair (Yellow and White), and R1 in series between the alarm pair and the tamper pair (Yellow and Brown). The panel zone connects to White and Blue.
Click to enlarge
≈ 1 kΩ: the NC contact is closed and shorts out R2. Only R1 remains in series.≈ 2 kΩ: the contact opens, R2 is no longer shorted. R1 and R2 are in series.∞ Ω: tamper triggered at the panel.2 kΩ, hence an alarm, and a short circuit there masks the opening of the contact. The tamper pair, for its part, triggers the tamper if it is cut.Points to watch
Sources: Galaxy Dimension installation manual (Honeywell), zone wiring · TILLYS CUBE, TILLYS NG and remote modules register list (GR-10005-FR, in French), § 3.2.
1 kΩ resistors: R2 in parallel across the alarm pair, R1 in series. Normal ≈ 1 kΩ, alarm ≈ 2 kΩ, cut ∞ Ω.0 Ω. A cut triggers the tamper at the panel.