Wiring a floor contact or door contact through a junction box with double EOL

6 April 2026 · updated 25 October 2026 · Theo

FRLire cette fiche en français
Schéma câblage Sabot : DO avec une BR
Click to enlarge
●
Difficulty: Beginner
⏱️
Reading time: ~3 min

A floor-mounted contact (“sabot”) or a door contact (DO) usually has 4 wires: one pair for the alarm circuit and one pair for the cable tamper.

When the cable goes through a junction box (BR on the diagram), the double EOL resistors are fitted in the junction box, which makes wiring and on-site diagnosis easier.

The panel then reads R1 in normal state and R1 + R2 in alarm. The principle, the ranges used by each panel and their settings are covered in the guide Double EOL zone balancing.

⚡
The essentials in 30 seconds
  • 4-wire floor contact or door contact: one alarm pair, one tamper pair.
  • Double EOL with 2 × 1 kΩ, fitted in the junction box.
  • Ohmmeter on the alarm pair: ≈ 1 kΩ in normal state, ≈ 2 kΩ in alarm, ∞ Ω if the cable is cut. Tamper pair: 0 Ω.
  • Never put R1 and R2 in series: the panel would not recognise the zone.

What you need

Item Specification
Contact typeFloor contact or door contact, 4 wires
Zone typeDouble EOL through a junction box
EOL resistors2 × 1 kΩ
Junction boxStandard junction box
Compatible withGalaxy GD-48 / GD-96 / GD-264 / GD-520 / TIL panel
Power supplyPassive: no power required

Ohmmeter reference values

State Measured value
Contact closed (normal)≈ 1 kΩ
Contact open (alarm)≈ 2 kΩ
Cable cut (tampering)∞ Ω (open circuit)
Tamper0 Ω (continuity)

Identifying the wires

Wires (in our example) Role
Yellow + White“Alarm” pair: EOL circuit
Brown + Blue“Tamper” pair: continuity
ℹ️
Identify both pairs before wiring
Measure with an ohmmeter from the floor contact or door contact:
  • Closed ≈ 1 kΩ / open ≈ 2 kΩ: this is the alarm pair.
  • Continuity (0 Ω): this is the tamper pair.

Wiring in the junction box

In the junction box, R2 is wired across the two wires of the alarm pair (Yellow and White), and R1 in series between the alarm pair and the tamper pair (Yellow and Brown). The panel zone connects to White and Blue.

Wiring diagram of a 4-wire floor contact or door contact through a junction box: alarm pair Yellow and White, tamper pair Brown and Blue, two 1 kΩ resistors in the junction box, and an ohmmeter test to identify the pairs

Click to enlarge

1
Normal (contact closed)
Measured resistance ≈ 1 kΩ: the NC contact is closed and shorts out R2. Only R1 remains in series.
2
Alarm (contact open)
Measured resistance ≈ 2 kΩ: the contact opens, R2 is no longer shorted. R1 and R2 are in series.
3
Cable cut between the junction box and the panel
Measured resistance ∞ Ω: tamper triggered at the panel.
4
Tamper pair sabotaged (cut)
Loss of continuity on Brown/Blue: tamper triggered at the panel.
!
Between the contact and the junction box
Since the resistors are in the junction box, the alarm pair between the contact and the junction box is not supervised like the rest of the line: a cut on this pair gives 2 kΩ, hence an alarm, and a short circuit there masks the opening of the contact. The tamper pair, for its part, triggers the tamper if it is cut.

Points to watch

!
Identify the pairs
Identify both pairs carefully before wiring: swapping the alarm and tamper pairs would leave the system not working.
!
Where the resistors go
R1 and R2 go in the junction box, on the contact side, not at the panel: fitted at the panel terminals, they leave the cable unsupervised (see the guide Double EOL zone balancing).
✕
R1 and R2 in series
Never put R1 and R2 in series: the normal value would be 2 kΩ instead of 1 kΩ and the panel will not recognise the zone.
ℹ️
Why use a junction box
It keeps the resistors in one accessible place, which makes diagnosis and replacement easier when something fails.

Sources: Galaxy Dimension installation manual (Honeywell), zone wiring · TILLYS CUBE, TILLYS NG and remote modules register list (GR-10005-FR, in French), § 3.2.

BR: junction box
Keeps the double EOL resistors in one accessible place, which makes wiring, diagnosis and replacement on site easier.
Double EOL
Two 1 kΩ resistors: R2 in parallel across the alarm pair, R1 in series. Normal ≈ 1 kΩ, alarm ≈ 2 kΩ, cut ∞ Ω.
Tamper
Pair of the cable dedicated to its own supervision: continuity 0 Ω. A cut triggers the tamper at the panel.