Wiring a 2-wire door contact or floor contact (no tamper pair) with double EOL

9 April 2026 · updated 25 October 2026 · Theo

FRLire cette fiche en français
Câblage DO : Sabot 2 fils (sans paire AP)(Double EOL)
Click to enlarge
●
Difficulty: Beginner
⏱️
Reading time: ~4 min

Some door contacts (DO) or floor-mounted contacts only have a single pair of wires (the alarm pair). The tamper pair (AP) is missing, either because the device is entry-level, or because a 2-conductor cable was laid during installation.

In that case, a double resistor (double EOL) wiring is still possible, supervising both the zone state and electrical tampering of the line (cut / short circuit), using only the 2 available wires.

The panel reads R1 in normal state and R1 + R2 in alarm. The principle, the ranges used by each panel and their settings are covered in the guide Double EOL zone balancing.

⚡
The essentials in 30 seconds
  • Two resistors on the loop: R2 (1 kΩ) in parallel with the contact, R1 (1 kΩ) in series, at the end of the line.
  • Normal 1 kΩ, alarm 2 kΩ, short circuit 0 Ω, cut ∞ Ω.
  • Both resistors go at the detector, never at the panel.
  • Limitation: opening the housing cover is not detected, since there is no tamper contact.

The two resistors

Double EOL on 2 wires means fitting two resistors on the loop. Each has a distinct role:

Resistor Position Role
R2: 1 kΩIn parallel with the contactTells an open zone from a closed zone
R1: 1 kΩIn series, at the end of the lineDetects a cable cut (∞ Ω)

The panel continuously reads the total resistance of the loop and interprets the 4 possible states:

Loop state Resistance seen Meaning
Zone closed (normal)R1 = 1 kΩ✅ Normal
Zone open (door open / floor contact lifted)R1+R2 = 2 kΩ⚠️ Zone alarm
Short circuit on the cable0 Ω🔴 Tamper or fault, depending on the panel
Cable cut∞ Ω🔴 Tamper
ℹ️
Values depend on the panel
The resistor values must match the zone setting: see the values and settings for each panel in the guide Double EOL zone balancing.

Where the resistors go

Since there is no tamper pair, both resistors must be fitted at the detector / contact, as far as possible from the panel:

Wiring diagram of a 2-wire door contact or floor contact without a tamper pair, double EOL: one 1 kΩ resistor in parallel across the contact, a second 1 kΩ in series on the loop back to the panel

Click to enlarge

R2
In parallel
In parallel across the terminals of the contact (door contact or floor contact), directly inside its housing.
R1
In series
In series in the loop, on the return side, at the same end (same housing or a junction close to the detector).
!
The whole length of the cable
This placement guarantees supervision of the whole length of the cable. A resistor fitted at the panel gives no protection against a cut or short circuit on the cable between the panel and the detector.

Limitations of this wiring

✕
Mechanical tampering not detected
Mechanical tampering with the housing (opening the cover) is not detected: there is no dedicated tamper contact.
✕
Electrical supervision only
Supervision is electrical only (cut / short circuit on the cable).
!
High security
For an installation with high security requirements, prefer a 4-wire contact or floor contact with a separate tamper pair.

Typical use cases

  • Replacement or extension on an existing 2-conductor cable
  • Temporary installation or low-criticality zone
  • Devices without a physical tamper contact

Sources: Galaxy Dimension installation manual (Honeywell), zone wiring · TILLYS CUBE, TILLYS NG and remote modules register list (GR-10005-FR, in French), § 3.2.

DO: door contact
Door contact or floor contact. Here, a model with a single pair of wires, the alarm pair.
AP: tamper (“auto protection”)
Separate tamper pair, missing in this setup: opening the housing cover is therefore not detected.
Double EOL
Two resistors on the loop, R2 in parallel with the contact and R1 in series, to tell normal, alarm, short circuit and cut apart.
2 filsdouble EOL