Wiring a 2-wire door contact or floor contact (no tamper pair) with double EOL
9 April 2026 · updated 25 October 2026 · Theo
FRLire cette fiche en français
Some door contacts (DO) or floor-mounted contacts only have a single pair of wires (the alarm pair). The tamper pair (AP) is missing, either because the device is entry-level, or because a 2-conductor cable was laid during installation.
In that case, a double resistor (double EOL) wiring is still possible, supervising both the zone state and electrical tampering of the line (cut / short circuit), using only the 2 available wires.
The panel reads R1 in normal state and R1 + R2 in alarm. The principle, the ranges used by each panel and their settings are covered in the guide Double EOL zone balancing.
- Two resistors on the loop: R2 (
1 kΩ) in parallel with the contact, R1 (1 kΩ) in series, at the end of the line. - Normal
1 kΩ, alarm2 kΩ, short circuit0 Ω, cut∞ Ω. - Both resistors go at the detector, never at the panel.
- Limitation: opening the housing cover is not detected, since there is no tamper contact.
The two resistors
Double EOL on 2 wires means fitting two resistors on the loop. Each has a distinct role:
| Resistor | Position | Role |
|---|---|---|
R2: 1 kΩ | In parallel with the contact | Tells an open zone from a closed zone |
R1: 1 kΩ | In series, at the end of the line | Detects a cable cut (∞ Ω) |
The panel continuously reads the total resistance of the loop and interprets the 4 possible states:
| Loop state | Resistance seen | Meaning |
|---|---|---|
| Zone closed (normal) | R1 = 1 kΩ | ✅ Normal |
| Zone open (door open / floor contact lifted) | R1+R2 = 2 kΩ | ⚠️ Zone alarm |
| Short circuit on the cable | 0 Ω | 🔴 Tamper or fault, depending on the panel |
| Cable cut | ∞ Ω | 🔴 Tamper |
Where the resistors go
Since there is no tamper pair, both resistors must be fitted at the detector / contact, as far as possible from the panel:
Click to enlarge
Limitations of this wiring
Typical use cases
- Replacement or extension on an existing 2-conductor cable
- Temporary installation or low-criticality zone
- Devices without a physical tamper contact
Sources: Galaxy Dimension installation manual (Honeywell), zone wiring · TILLYS CUBE, TILLYS NG and remote modules register list (GR-10005-FR, in French), § 3.2.