Vanderbilt ÖFK-200 hold-up button on an SPC panel: wiring and connection

28 October 2026 · updated 29 October 2026 · Theo

FRLire cette fiche en français
●●
Difficulty: Intermediate
⏱️
Reading time: ~7 min

The Vanderbilt ÖFK-200 is a mechanical hold-up button with an NC contact. On an SPC panel, it connects to a zone with 1 kΩ double EOL, its tamper on the same pair. SPC labels are quoted as they appear on a panel set to French, with their meaning.

The ÖFK-200 stays latched after being pressed, and its red LED, powered from the panel's 0 V and 12 V, shows that it has been pressed. The ÖFK-200-N returns to rest on its own and has no LED.

⚡
The essentials in 30 seconds
  • Zone: terminal 3 to I1, terminal 6 to C.
  • Inside the button: R2 of 1 kΩ between 3 and 4, R1 of 1 kΩ from 4 to 7.
  • Readings: 1 kΩ at rest, 2 kΩ with the button pressed, infinite with the cover open.
  • LED (ÖFK-200): terminal 2 to 12V, terminal 1 to 0V.
  • SPC: double EOL 1K / 1K (the factory setting is 4K7 / 4K7), zone type Alarme agression (hold-up).

The principle

1
At rest, the panel reads 1 kΩ
The button's NC contact is closed and shorts out R2, the alarm resistor. The measuring current only goes through R1, in series, and the closed tamper.
2
Button pressed: 2 kΩ
The contact opens, the current also goes through the alarm resistor. The hold-up zone triggers, silent by default, and the event is sent whatever the panel's mode.
3
The LED shows the button was pressed
On the ÖFK-200, the red LED stays on as long as the button stays latched. It takes its power from the panel's 0 V and 12 V, and its 470 Ω resistor is built in.
Situation The panel reads
Normal1 kΩ: input closed
Button pressed2 kΩ: input open
Cover open or cable cutInfinite: input disconnected
Cable shortedLess than 300 Ω: short circuit

With 1K / 1K double EOL, the SPC accepts normal from 700 Ω to 1.3 kΩ and alarm from 1.5 to 2.6 kΩ. Outside these ranges, it treats the input as disconnected.

Simulator

Choose the model, then trigger each situation. On the ÖFK-200, the press stays latched: a second click resets the button. On the ÖFK-200-N, the contact only opens while the button is pressed.

Resistance read1 kΩ
Input I1Closed
ButtonNormal
LEDOff

Normal: the NC contact shorts out the alarm resistor. The panel reads 1 kΩ.

Vanderbilt ÖFK-200 hold-up button on an SPC panel: terminals 3 and 6 to zone I1 and C, alarm resistor R2 of 1 kΩ between 3 and 4, series resistor R1 of 1 kΩ from 4 to 7, tamper between 6 and 7, LED between 12 V and 0 V Vanderbilt ÖFK-200 housing open 5 6 7 Tamper LED 470 Ω 1 − 2 + 3 C 4 NC R2 1k R1 1k Cable 0V 12V I1 C I2 Auxiliary output Zone inputs SPC controller I1: Closed
Zone I1 loop +12 V auxiliary 0 V Current flowing Open circuit Cut or short circuit Button to LED contact R2, 1 kΩ, terminals 3 and 4: alarm resistor, in parallel across the NC contact. R1, 1 kΩ, terminals 4 and 7: resistor in series in the loop.

Terminals and wiring

ÖFK terminal Role
1LED −, ÖFK-200 only
2LED +, ÖFK-200 only
3Common of the alarm contact
4Normally closed (NC) side of the alarm contact
5Free
6 and 7NC tamper, closed by the cover
Connection To
Zone, double EOL
Terminal 3SPC I1
Terminal 6SPC C (common of I1 and I2)
R2, 1 kΩ (alarm)Between terminals 3 and 4
R1, 1 kΩ (series)From terminal 4 to terminal 7
LED, ÖFK-200 only
Terminal 2 (+)12V, auxiliary output
Terminal 1 (−)0V, auxiliary output

Both resistors are fitted inside the button housing, on its terminals. The cable to the panel is thus supervised: a short circuit or a cut shows up.

⚡
Electrical ratings
  • LED: 9 to 15 V DC, 470 Ω built in. The SPC's 12 V is suitable, with no resistor to add.
  • Contacts: 30 V DC, 100 mA for the alarm; 35 V, 50 mA for the tamper.
  • SPC auxiliary output: 12 V DC, 750 mA maximum for everything it powers.

The ÖFK-200-N is wired the same way, without terminals 1 and 2.

Programming the SPC

Everything is set in the web interface, in installer mode, under Configuration > Hardware > Centrale (controller).

1
Input double EOL
Set input 1 to double résistance 1K / 1K (double EOL 1K / 1K; “2 RÉSIST. 1K / 1K” on the keypad). The factory value is 4K7 / 4K7. Do not tick the Normalement ouvert (normally open) attribute: the button's contact is NC.
2
Zone type
Name the zone (16 characters maximum) and choose the type Alarme agression (hold-up). The zone is active 24 hours a day, and the Silencieux (silent) attribute is set by default.

The ÖFK-200 LED needs no programming: it is powered by the auxiliary output.

Commissioning checks

  • With an ohmmeter, I1 and C wires disconnected: 1 kΩ at rest, 2 kΩ with the button pressed, infinite with the cover removed.
  • In the web interface, under État > Entrées > Toutes les zones (status, inputs, all zones): the Tolérance R. (resistance tolerance) column must show Bon (good).
  • Real press: the input goes Ouverte (open), the hold-up event goes to the monitoring centre, and the ÖFK-200 LED lights up.
  • To finish: reset the button and check that the input returns to Fermée (closed).

Common pitfalls

✕
Resistors at the panel terminals
The zone reads 1 kΩ, but the cable is no longer supervised: a short circuit on the line passes for normal and defeats the button.
!
Input left at 4K7 / 4K7
With 1 kΩ resistors, the panel reads 1 kΩ at rest, below the 4K7 normal range (3.3 to 6.1 kΩ): the input goes disconnected. Set the input to 1K / 1K.
!
Tamper left out
Terminals 6 and 7 outside the loop: opening the cover no longer shows. They must be in series, between R1 and the common.
!
LED reversed
Terminals 1 and 2 swapped, the LED never lights up. Terminal 2 goes to 12 V, terminal 1 to 0 V.
!
Zone left as type Alarme (alarm)
The button triggers an intrusion alarm, not a hold-up: that is not the event the monitoring centre expects.

Sources: Vanderbilt ÖFK-200 & ÖFK-200-N datasheet (2016) · SPC 3.11, wiring the zone inputs · controller hardware · zone types (SPC manual in French).

Glossary
Double EOL
Zone wired with two resistors: one in series, the other in parallel across the contact. The panel tells normal, alarm, cut and short circuit apart.
Tamper
Contact closed as long as the cover is in place. Opening it cuts the loop.
Latching button
Button that stays pressed in after being pressed, contact open, until it is reset. The ÖFK-200 resets without a key.
Auxiliary output
0 V and 12 V terminals of the SPC board, which power the connected devices, here the button's LED.
24-hour zone
Zone supervised at all times, whether the panel is set or unset.