Vanderbilt ÖFK-200 hold-up button on an SPC panel: wiring and connection
28 October 2026 · updated 29 October 2026 · Theo
FRLire cette fiche en françaisThe Vanderbilt ÖFK-200 is a mechanical hold-up button with an NC contact. On an SPC panel, it connects to a zone with 1 kΩ double EOL, its tamper on the same pair. SPC labels are quoted as they appear on a panel set to French, with their meaning.
The ÖFK-200 stays latched after being pressed, and its red LED, powered from the panel's 0 V and 12 V, shows that it has been pressed. The ÖFK-200-N returns to rest on its own and has no LED.
- Zone: terminal 3 to
I1, terminal 6 toC. - Inside the button: R2 of 1 kΩ between 3 and 4, R1 of 1 kΩ from 4 to 7.
- Readings: 1 kΩ at rest, 2 kΩ with the button pressed, infinite with the cover open.
- LED (ÖFK-200): terminal 2 to
12V, terminal 1 to0V. - SPC: double EOL 1K / 1K (the factory setting is 4K7 / 4K7), zone type Alarme agression (hold-up).
The principle
| Situation | The panel reads |
|---|---|
| Normal | 1 kΩ: input closed |
| Button pressed | 2 kΩ: input open |
| Cover open or cable cut | Infinite: input disconnected |
| Cable shorted | Less than 300 Ω: short circuit |
With 1K / 1K double EOL, the SPC accepts normal from 700 Ω to 1.3 kΩ and alarm from 1.5 to 2.6 kΩ. Outside these ranges, it treats the input as disconnected.
Simulator
Choose the model, then trigger each situation. On the ÖFK-200, the press stays latched: a second click resets the button. On the ÖFK-200-N, the contact only opens while the button is pressed.
Normal: the NC contact shorts out the alarm resistor. The panel reads 1 kΩ.
Terminals and wiring
| ÖFK terminal | Role |
|---|---|
| 1 | LED −, ÖFK-200 only |
| 2 | LED +, ÖFK-200 only |
| 3 | Common of the alarm contact |
| 4 | Normally closed (NC) side of the alarm contact |
| 5 | Free |
| 6 and 7 | NC tamper, closed by the cover |
| Connection | To |
|---|---|
| Zone, double EOL | |
| Terminal 3 | SPC I1 |
| Terminal 6 | SPC C (common of I1 and I2) |
| R2, 1 kΩ (alarm) | Between terminals 3 and 4 |
| R1, 1 kΩ (series) | From terminal 4 to terminal 7 |
| LED, ÖFK-200 only | |
| Terminal 2 (+) | 12V, auxiliary output |
| Terminal 1 (−) | 0V, auxiliary output |
Both resistors are fitted inside the button housing, on its terminals. The cable to the panel is thus supervised: a short circuit or a cut shows up.
- LED: 9 to 15 V DC, 470 Ω built in. The SPC's 12 V is suitable, with no resistor to add.
- Contacts: 30 V DC, 100 mA for the alarm; 35 V, 50 mA for the tamper.
- SPC auxiliary output: 12 V DC, 750 mA maximum for everything it powers.
The ÖFK-200-N is wired the same way, without terminals 1 and 2.
Programming the SPC
Everything is set in the web interface, in installer mode, under Configuration > Hardware > Centrale (controller).
The ÖFK-200 LED needs no programming: it is powered by the auxiliary output.
Commissioning checks
- With an ohmmeter,
I1andCwires disconnected: 1 kΩ at rest, 2 kΩ with the button pressed, infinite with the cover removed. - In the web interface, under État > Entrées > Toutes les zones (status, inputs, all zones): the Tolérance R. (resistance tolerance) column must show Bon (good).
- Real press: the input goes Ouverte (open), the hold-up event goes to the monitoring centre, and the ÖFK-200 LED lights up.
- To finish: reset the button and check that the input returns to Fermée (closed).
Common pitfalls
Sources: Vanderbilt ÖFK-200 & ÖFK-200-N datasheet (2016) · SPC 3.11, wiring the zone inputs · controller hardware · zone types (SPC manual in French).