Sewosy PLS1224 status indicator on Galaxy: wiring through an AWZ529 relay

20 October 2026 · updated 28 October 2026 · Theo

FRLire cette fiche en français
●●
Difficulty: Intermediate
⏱️
Reading time: ~6 min

A status indicator at the entrance of a room shows the alarm state before you go in: green when unset, red when set.

Here, a Sewosy PLS1224 indicator panel is driven by an output of a Galaxy RIO, through the Pulsar AWZ529 relay module. Galaxy menu labels are quoted as they appear on a keypad set to French, with their meaning.

The relay turns the RIO output into a two-position dry contact: one lights the green, the other the red.

⚡
The essentials in 30 seconds
  • Coil: +12 V on I1 +, RIO output on I1 −.
  • Contacts: C1 → COM, NC1 → NO V, NO1 → NO R. Dry contact, no voltage.
  • Indicator panel: 12/24 V non-polarised, on the +12 V and 0 V of the RIO.
  • Output: MES Totale (full set), positive polarity, follow mode, group to display.
  • Jumper: fitted, steady green; without it, the green flashes.

The principle

1
The RIO output
A transistor connected to 0 V (open collector), pulled up to +12 V through 3.3 kΩ. In positive polarity: +12 V at rest, 0 V once active. 400 mA maximum.
2
The relay
Its coil sits between the +12 V and the output: it only pulls in with the output at 0 V. The common C1 then switches from NC1 (green) to NO1 (red).
3
The indicator panel
It does not light up by receiving a voltage: it has its own control terminals. COM–NO V closed: green. COM–NO R closed: red.

Simulator

Choose the output polarity, then set the group. “Jumper” removes or refits the indicator panel's jumper, “Auto cycle” sets and unsets in a loop.

RIO output+12 V
RelayC1 → NC1
LightGreen

Unset: output at +12 V, the coil is not powered. C1 on NC1: green light.

Status indicator wiring: Galaxy RIO output, Pulsar AWZ529 relay module and Sewosy PLS1224 indicator panel Galaxy RIO C072 3.3 kΩ OC output 0V +12V Output Pulsar AWZ529 relay L1 MP2 L2 Relay 2 unused − I1 + NO1 NC1 C1 − I2 + NO2 NC2 C2 Sewosy PLS1224 NO R NO V 12/24V COM Jumper Red Green
+12 V 0 V RIO output C1 to COM NC1 to NO V (green) NO1 to NO R (red) Current in the coil Contact open

Hardware and wiring

Item Key facts
Galaxy RIOFour open-collector outputs, 400 mA. Supply 10.5 to 16 V, 40 mA.
Pulsar AWZ529 (MP2)Two changeover relays. Coil 10 to 14 V DC, 37 mA. Contacts 2 A, 30 V DC or 48 V AC.
Sewosy PLS1224Red and green LEDs. 12/24 V AC/DC non-polarised, 50 mA. IP42, indoor use only.

On the AWZ529, LEDs L1 and L2 show which relays are energised.

Terminal to terminal

From To
Relay coil
RIO +12VI1 +
RIO Sortie (output)I1 −
Indicator panel power
RIO +12VPLS1224 12/24V
RIO 0VPLS1224 12/24V, either way round
Indicator panel control
C1COM: common
NC1NO V: green, relay at rest
NO1NO R: red, relay energised
  • Both +12 V feeds (coil and indicator panel) come from the same RIO terminal.
  • The module's relay 2 stays free.
  • Indicator panel terminals, in order: 12/24V, 12/24V, NO R, COM, NO V. The reading direction depends on how you hold the board: go by the printed markings.
!
No voltage on C1 or COM
The indicator panel is driven by a dry contact. For a light powered through the contact, the common receives +12 V; not here: C1 goes to COM and nowhere else.

Programming the output

On the keypad: menu 53 = Prog. Sorties (program outputs), function 09 MES Totale (full set) on a Galaxy Dimension. In the software: RIO outputs window.

Setting Value
FunctionMES Totale (full set)
PolarityPositive
ModeAsservie (follow)
GroupsThe room's group
  • MES Totale (full set): active when the associated groups are set.
  • Positive: +12 V at rest, 0 V once active: the coil only pulls in when set.
  • Asservie (follow): the output follows the setting and unsetting of the group.
  • Group: the indicator shows the state of this group.
!
The full set output is not positive out of the box
On a Galaxy Dimension, all outputs are in positive polarity by default, except full set (09). Without changing this setting, the light is red when unset and green when set.

Checks

1
Group unset
Green light, L1 off. Between the RIO output and 0 V: +12 V.
2
Full set
The output goes to 0 V, L1 lights up, the light turns red.
3
Unset
L1 goes off, the light turns green again. If it flashes, fit the jumper.

Common pitfalls

✕
+12 V brought to C1
The indicator panel expects a dry contact. The common goes to COM, with no voltage.
!
Colours reversed
Output left in negative polarity: 0 V at rest, the coil pulls in when unset. Switch to positive.
!
The light does not follow the group
In latched mode (“mémorisé”), the output waits for a valid code; in pulsed mode (“pulsé”), it only lasts the programmed time. You need follow mode and the right group.
!
The relay never pulls in
I1 + to +12 V, I1 − to the output. L1 must light up when setting.
!
The green flashes
Without the jumper, the green LED flashes. With it, it stays steady.

Sources: MP2 AWZ529 relay module manual (Pulsar, French edition) · PLS range indicator panels manual (Sewosy) · Galaxy Dimension installation manual (Honeywell), RIO outputs and option 53.

Glossary
Open-collector output (OC)
Transistor output that connects the load to 0 V when active. On the RIO, a 3.3 kΩ resistor pulls it up to +12 V the rest of the time.
Dry contact
Contact that supplies no voltage: it simply opens or closes a circuit.
Changeover contact
Contact with three terminals: at rest, the common C is connected to NC; with the relay energised, it is connected to NO.
Follow mode (“asservie”)
The output follows the activity of its source: here, the setting and unsetting of the group.
Positive polarity
Output at +12 V at rest and 0 V once active. Negative polarity does the opposite.