Wiring 2 door contacts or floor contacts through one junction box with double EOL
6 April 2026 · updated 25 October 2026 · Theo
FRLire cette fiche en français
When two floor contacts or door contacts (DO) are close to each other (double door, double-leaf gate…), they can be connected to a single junction box (BR on the diagram) and use only one zone on the panel.
The alarm pairs of both contacts are put in series in the junction box, and so are the tamper pairs, which simplifies the wiring and reduces the number of zones used.
The panel reads R1 in normal state and R1 + R2 as soon as a contact opens. The principle, the ranges used by each panel and the other ways of wiring several contacts on one zone are covered in the guide Double EOL zone balancing.
- Two floor contacts or door contacts with 4 wires each, a single double EOL zone on the panel.
- In the junction box: alarm pairs in series with R2 (
1 kΩ) in parallel and R1 (1 kΩ) in series, tamper pairs in series. - Ohmmeter:
≈ 1 kΩwith both contacts closed,≈ 2 kΩas soon as one contact opens,∞ Ωif the cable is cut. - One zone for two contacts: no way of knowing which one triggered.
What you need
| Item | Specification |
|---|---|
| Contacts | 2 × floor contact or door contact, 4 wires each |
| Zone type | Double EOL: 1 zone for 2 contacts |
| EOL resistors | 2 × 1 kΩ (in the junction box) |
| Junction box | Standard junction box |
| Compatible with | Galaxy GD-48 / GD-96 / GD-264 / GD-520 / TIL panel |
| Power supply | Passive: no power required |
Ohmmeter reference values
| State | Measured value |
|---|---|
| Both contacts closed (normal) | ≈ 1 kΩ |
| One contact open (alarm) | ≈ 2 kΩ |
| Cable cut (tampering) | ∞ Ω (open circuit) |
| Tamper | 0 Ω (continuity) |
Identifying the wires, per contact
| Cables | Role |
|---|---|
| Alarm pair 1 + alarm pair 2 | “Alarm” pair: EOL circuit |
| Tamper pair 1 + tamper pair 2 | “Tamper” pair: continuity |
- Closed ≈ 1 kΩ / open ≈ 2 kΩ: alarm pair.
- Continuity (0 Ω): tamper pair.
Wiring 2 contacts in one junction box
In the junction box, the cables of both contacts are brought together:
Click to enlarge
1 kΩ) in parallel across the whole and R1 (1 kΩ) in series. If either contact opens, the zone triggers.2 kΩ, hence an alarm, and a short circuit there masks the opening of the contact. The tamper pairs, for their part, trigger the tamper if they are cut.Points to watch
Sources: Galaxy Dimension installation manual (Honeywell), zone wiring · TILLYS CUBE, TILLYS NG and remote modules register list (GR-10005-FR, in French), § 3.2.
0 Ω. Both tamper pairs are put in series in the junction box.