Legrand 0 785 51 status indicator on Galaxy: wiring through an AWZ529

23 October 2026 · updated 28 October 2026 · Theo

FRLire cette fiche en français
●●
Difficulty: Intermediate
⏱️
Reading time: ~6 min

A status indicator at the entrance of a room shows the alarm state before you go in: green when unset, red when set.

Here, two Legrand Mosaic 0 785 51 lights are driven by an output of a Galaxy RIO, through the Pulsar AWZ529 relay module. Galaxy menu labels are quoted as they appear on a keypad set to French, with their meaning.

The relay switches the RIO's +12 V to one light or the other: green at rest, red when it pulls in.

⚡
The essentials in 30 seconds
  • Coil: +12 V on I1 +, RIO output on I1 −.
  • Contacts: +12 V on C1, NC1 → green light, NO1 → red light. The contact carries the lights' +12 V.
  • Return: the other terminal of both lights to the RIO's 0 V.
  • Colour: white LED; the label slipped under the window gives the light its colour.
  • Output: MES Totale (full set), positive polarity, follow mode, group to display.

The principle

1
The RIO output
A transistor connected to 0 V (open collector), pulled up to +12 V through 3.3 kΩ. In positive polarity: +12 V at rest, 0 V once active. 400 mA maximum.
2
The relay
Its coil sits between the +12 V and the output: it only pulls in with the output at 0 V. The common C1, at +12 V, then switches from NC1 (green) to NO1 (red). The output only carries the coil: 37 mA.
3
The lights
No control input: a 0 785 51 lights up as soon as its two terminals receive its voltage, 12 to 24 V, AC or DC. The contact brings them the +12 V, the return goes to 0 V.

Simulator

Choose the output polarity, then set the group. “Auto cycle” sets and unsets in a loop.

RIO output+12 V
RelayC1 → NC1
LightGreen

Unset: output at +12 V, the coil is not powered. C1 on NC1: green light.

Status indicator wiring: Galaxy RIO output, Pulsar AWZ529 relay module and two Legrand Mosaic 0 785 51 lights Galaxy RIO C072 3.3 kΩ OC output 0V +12V Output Pulsar AWZ529 relay L1 MP2 L2 Relay 2 unused − I1 + NO1 NC1 C1 − I2 + NO2 NC2 C2 Legrand 0 785 51 1 2 Green 1 2 Red
+12 V 0 V RIO output NC1 to the green NO1 to the red Current flowing Contact open, no current

Hardware and wiring

Item Key facts
Galaxy RIOFour open-collector outputs, 400 mA. Supply 12 V (10.5 to 16 V), 40 mA.
Pulsar AWZ529 (MP2)Two changeover relays. Coil 10 to 14 V DC, 37 mA. Contacts 2 A, 30 V DC or 48 V AC.
Legrand Mosaic 0 785 51, two unitsSingle 1-module light, white LED. 12 to 24 V, AC 50/60 Hz or DC, 0.2 W at 24 V. IP41, from −5 to +35 °C.
  • On the AWZ529, LEDs L1 and L2 show which relays are energised.
  • Each light has a pivoting window and four labels supplied: red, orange, green, blue.
  • Screw terminals of the lights: 1 × 2.5 mm² or 2 × 1.5 mm², strip 8 mm. Fitted on a support, with a Mosaic cover plate.

Terminal to terminal

From To
Relay coil
RIO +12VI1 +
RIO Sortie (output)I1 −
Relay contact
RIO +12VC1: +12 V of the lights
NC1Green light, terminal 1: relay at rest
NO1Red light, terminal 1: relay energised
Lights return
RIO 0VGreen and red lights, terminal 2
  • Both +12 V feeds (coil and C1) come from the same RIO terminal.
  • The 0 V can loop from one light to the other: each terminal takes two 1.5 mm² wires.
  • The module's relay 2 stays free.
!
Here, C1 receives the +12 V
The relay contact powers the lights: the +12 V goes through C1, then through NC1 or NO1. It is the opposite of a dry-contact indicator panel such as the Sewosy PLS1224, whose common receives no voltage.
⚡
The colour comes from the label
Both lights are identical, with a white LED. Green label under the window of the NC1 light, red under the window of the NO1 light. The orange and blue ones are kept spare.

Programming the output

On the keypad: menu 53 = Prog. Sorties (program outputs), function 09 MES Totale (full set) on a Galaxy Dimension. In the software: RIO outputs window.

Setting Value
FunctionMES Totale (full set)
PolarityPositive
ModeAsservie (follow)
GroupsThe room's group
  • MES Totale (full set): active when the associated groups are set.
  • Positive: +12 V at rest, 0 V once active: the coil only pulls in when set.
  • Asservie (follow): the output follows the setting and unsetting of the group.
  • Group: the indicator shows the state of this group.
!
The full set output is not positive out of the box
On a Galaxy Dimension, all outputs are in positive polarity by default, except full set (09). Without changing this setting, the light is red when unset and green when set.

Checks

1
Group unset
Green light, L1 off. Between the RIO output and 0 V: +12 V. Between terminal 1 of the green light and 0 V as well.
2
Full set
The output goes to 0 V, L1 lights up, red replaces green.
3
Unset
L1 goes off, the red goes off, the green comes back on.

Common pitfalls

✕
230 V light instead of 12-24 V
The 0 785 01, in the same format, is the 230 V version. Check the part number: 0 785 51 for 12-24 V.
!
Colours reversed
Output left in negative polarity: 0 V at rest, the coil pulls in when unset. Switch to positive. If the polarity is right: the green label goes on the NC1 light.
!
No light on
No +12 V on C1, or no 0 V on terminals 2. If L1 follows the group, the relay is working: look at the lights side.
!
The light does not follow the group
In latched mode (“mémorisé”), the output waits for a valid code; in pulsed mode (“pulsé”), it only lasts the programmed time. You need follow mode and the right group.
!
The relay never pulls in
I1 + to +12 V, I1 − to the output. L1 must light up when setting.

Sources: MP2 AWZ529 relay module manual (Pulsar, French edition) · Mosaic 0 785 01/02/51/52 lights datasheet and Legrand 2022 catalogue, p. 899 (French editions) · Galaxy Dimension installation manual (Honeywell), RIO outputs and option 53.

Glossary
Open-collector output (OC)
Transistor output that connects the load to 0 V when active. On the RIO, a 3.3 kΩ resistor pulls it up to +12 V the rest of the time.
Changeover contact
Contact with three terminals: at rest, the common C is connected to NC; with the relay energised, it is connected to NO.
Follow mode (“asservie”)
The output follows the activity of its source: here, the setting and unsetting of the group.
Positive polarity
Output at +12 V at rest and 0 V once active. Negative polarity does the opposite.
Mosaic
Legrand wiring device range in 22.5 mm modules, fitted on a support and finished with a cover plate.