RS485 bus in intruder alarm systems: how it works and its limits
30 May 2026 · updated 25 October 2026 · Theo
FRLire cette fiche en françaisRS485 is the standard wired communication protocol used to connect keypads, expansion modules and peripherals to intruder alarm control panels.
It carries several communications on the same twisted pair over distances of up to 1200 m.
Many professional panels use RS485 as their field bus: Paradox (Digiplex EVO bus), Ajax (Fibra protocol), Satel (Integra/Versa) and Vanderbilt (SPC).
The physical layer is standardised, but each manufacturer runs its own application protocol on top of it.
- RS485 is a 2-wire differential bus (A and B), resistant to electromagnetic interference.
- Mandatory topology: daisy chain (in-line chain). Star wiring degrades communications.
120 Ωtermination resistor at both ends of the bus only.- Maximum distance: 1200 m at 100 kbps. In practice, 300 to 600 m covers almost every site.
- Used in particular by Paradox (Digiplex EVO), Ajax (Fibra) and Satel (Integra).
RS485 physical layer
RS485 (EIA-485) is a differential serial communication standard. Communication relies on two wires: A (or +) and B (or −).
The signal value is given by the voltage difference between A and B, which makes the transmission very resistant to electromagnetic interference and to voltage drop along the cable.
| Parameter | Value |
|---|---|
| Number of signal wires | 2 (A and B) — twisted pair recommended |
| Differential voltage | +200 mV to +6 V (state 1) / −200 mV to −6 V (state 0) |
| Typical data rate in alarm systems | 9,600 to 38,400 bps depending on the manufacturer |
| Maximum distance | 1200 m at 100 kbps |
| Number of nodes | 32 standard unit loads (more with high-impedance transmitters) |
| Topology | Daisy chain (line) — no star topology |
In intruder alarm systems, the data rate used by manufacturers is far below the theoretical maximum, which maximises range and tolerance to lower-quality cable.
Topology and cabling
RS485 is designed for a line (daisy chain) topology: the panel is at one end, the peripherals follow one another in series, and the last peripheral is at the other end of the bus.
Each peripheral is connected directly to the pair, without a branch.
Block diagram: Panel → Peripheral 1 → Peripheral 2 → Peripheral 3 [120 Ω termination]
Short branches (stubs) are tolerated if they are under 1 m long. Beyond that, they create reflections that degrade the signal quality.
Recommended cable
Use a shielded twisted pair (STP) of 0.5 mm² to 0.75 mm² for long distances. Standard 2-pair shielded alarm cables are suitable.
The shield must be connected to ground at the panel end only, to avoid ground loops.
Termination and biasing
Termination resistor
A 120 Ω termination resistor must be fitted at both ends of the bus. It absorbs signal reflections at the end of the line.
Without termination, reflections add up and corrupt the data even on moderate cable lengths.
On professional panels and peripherals, the termination resistor can usually be enabled with a jumper or a DIP switch on the PCB.
Check the documentation of each peripheral.
Biasing resistors
When there is no communication (idle state), wires A and B can float at undefined voltages and cause receive errors. Biasing resistors (pull-up on A, pull-down on B) hold the bus in a defined state at rest.
These resistors are usually built into the panel and do not need to be added by hand on typical installations.
RS485 on Paradox (Digiplex EVO)
Paradox panels of the EVO range (EVO48, EVO96, EVO192) and MG use the Digiplex EVO bus, which relies on RS485 at the physical level. This bus connects the keypads (K32+, TM50), the zone expansion modules (ZX8), the output modules (PGM96) and the communication modules.
| Parameter | Paradox Digiplex EVO value |
|---|---|
| Data rate | 9,600 / 19,200 bps depending on the module |
| Maximum number of modules | 32 per bus |
| Recommended distance | up to 300 m (unshielded cable) / 1000 m (shielded cable) |
| Wiring | 4 wires: GRN (data), YEL (data), RED (12 V), BLK (ground) |
| Termination | Jumper J1 to enable on the last module of the line |
The Digiplex EVO bus is proprietary at the application level.
Each module is addressed with DIP switches on the PCB (addresses 1 to 15 depending on the type). The panel scans the addresses automatically at start-up (auto-enrolment).
RS485 on Ajax (Fibra)
The Ajax Systems Fibra range is the wired version of the Ajax detectors. The Fibra protocol uses RS485 as its physical layer. The Ajax Hub 2 Plus acts as master, and the Fibra detectors and modules are the slaves.
| Parameter | Ajax Fibra value |
|---|---|
| Data rate | 38,400 bps |
| Number of Fibra lines per Hub | 4 independent lines |
| Number of devices per line | up to 100 |
| Maximum distance | 2000 m per line (0.5 mm² shielded twisted cable) |
| Wiring | 4 wires: A, B (RS485 data) + 12 V + GND |
Each Fibra line is an independent RS485 bus.
Devices are enrolled in the hub through the Ajax app and have no physical addressing DIP switch.
Daisy-chain topology is required, with a 120 Ω termination that can be enabled on the last device of each line.
5.6 kΩ EOL resistors for zone supervision. This value differs from the Honeywell (1 kΩ) or Paradox (1 kΩ) standards. Do not substitute other values.Distance and limits
The theoretical maximum distance of RS485 is 1200 m at 100 kbps. Several practical factors reduce this range:
| Factor | Impact | Solution |
|---|---|---|
| Non-twisted cable | Significant reduction of the reliable distance | Shielded twisted pair |
| Conductor size < 0.22 mm² | Voltage drop, errors from 200-300 m | 0.5 mm² minimum for long distances |
| Branches (stubs) > 1 m | Reflections, intermittent errors | Rewire as a daisy chain |
| High-voltage cables nearby | Random errors, disconnections | Separate cable route, shield grounded |
| Ground loops | Stray currents on the shield | Connect the shield at the panel end only |
For distances over 600 m or in noisy environments, an RS485 repeater or a galvanic isolator is recommended.
Troubleshooting
An intermediate device with termination enabled causes errors along the whole line.
The RS485 bus is not symmetrical: A must be connected to A and B to B on every device. Some manufacturers label the terminals + and −.
If the voltage is close to 0 V or negative, the biasing resistors are missing or too weak.
If communication comes back, reconnect the peripherals one by one to find the faulty peripheral or the problem branch.
If an AC voltage is detectable, connect the shield at one end only (panel end) to remove the ground loop.