ATLS THE VOICE EXT siren: wiring and programming

15 August 2026 · updated 25 October 2026 · Theo

FRLire cette fiche en français
Câblage sirène extérieur
Click to enlarge
●○
Difficulty: Intermediate
⏱️
Reading time: ~10 min

The THE VOICE EXT is an external siren with a voice speaker made by ATLS, ALTEC range. It combines three functions: an alarm tone compliant with the French standard NF C 48-265, an LED strobe, and voice message playback.

On a standard intruder installation, a single input is wired: SIR. It receives the trigger command from the siren output of the panel.

The message inputs IN1 to IN4 and the signalling input 1/0 are for other uses, mainly PPMS (French lockdown and emergency plans for schools). They are not covered here.

The physical connection is limited to five conductors. The difficulty lies elsewhere: the SIR input must be set to match exactly the logic of the panel output. A polarity or mode error gives a siren in permanent alarm as soon as it is powered up.

⚡
The essentials in 30 seconds
  • Power on DC 12-24, range 10 to 30 V DC. Optional 12 V – 2 Ah lead-acid battery.
  • SIR input set at the factory to PO+ / NC: +12 V at rest, 0 V or open circuit in alarm.
  • Default tone of an EXT: S02. S01 is the indoor tone, not to be confused with it.
  • Tamper AP TAMPER: normally closed loop, in series on the panel tamper loop.
  • Strobe set at the end of the SIR menu: FL0 disabled, FL1 enabled.

Connection terminals

All the voltages on the terminals are SELV (safety extra-low voltage) as defined by EN 60950.

Terminal Function Factory setting
SIR Triggers the alarm tone PO+ / NC
IN1 to IN4 Trigger messages 1 to 4 PO+ / NC
1/0 On / off signalling. One message on activation, a second one on reset PO+ / NC
BLK Switches a +12 V while a message is playing, to block the other sirens on the site —
A B C D RS-485 master / slave bus: commands and audio files —
DC 12-24 External power supply 10 to 30 V DC —
AP TAMPER Normally closed tamper loop NC
ℹ️
Single siren or master siren
With a single siren, DIP 1 stays OFF. The inputs are only wired on the master unit. On a slave (DIP 1 ON), the inputs change role: connected to 0 V, they block the matching message instead of triggering it.

Power supply, battery and tamper

The supply range is 10 to 30 V DC. The siren can therefore be connected either to a 12 V panel or to a 24 V power supply. The SICB charging circuit manages the battery over the whole range.

Configuration Max current on DC 12-24 DIP 3 position
With internal battery 500 mA with a flat battery OFF
Without internal battery 2 A ON

The backup battery is a 12 V – 2 Ah lead-acid battery, not supplied. With internal batteries, a 2 A charger powers up to four sirens wired in series, minimum conductor size 0.5 mm².

The tamper covers cover opening and removal from the wall. It relies on a microswitch rated 12 V DC / 5 A. The AP TAMPER output is wired in series on the panel tamper loop.

!
Common grounds
The 0 V of every device must be connected together. A siren powered separately, with no ground link to the panel, has its SIR input at a floating potential. Triggering becomes unpredictable.

Wiring the SIR input

Five conductors are enough: two for power, one for the command, two for the tamper.

Siren terminal Panel destination
DC 12-24 (+)Permanent +12 V auxiliary output
DC 12-24 (−)Common 0 V
SIRExternal siren output
AP TAMPERTamper loop, in series
Wiring diagram of the ATLS THE VOICE EXT external siren: DC 12-24 power, SIR input and AP TAMPER loop to the alarm panel

Click to enlarge

Polarity and mode

The SIR input is set on two independent criteria. The polarity defines which level counts: PO+ or PO-. The mode defines the direction of the change of state: NC or NO.

Combined, they give four cases.

Polarity Mode Rest state Alarm state
PO+ / NC Factory 12 V DC 0 V DC or nothing
PO+ / NO — 0 V DC or nothing 12 V DC
PO- / NC — 0 V DC 12 V DC or nothing
PO- / NO — 12 V DC or nothing 0 V DC

The difference between “0 V” and “nothing” is decisive. Nothing means a high-impedance state, typically an open-collector output without a pull-up.

Direct consequence: an output that applies no potential at rest is not suitable for PO+ / NC. This setting requires a clean +12 V.

Electrical parameter Value
Command threshold in negative polarity< 2 V DC
Command threshold in positive polarity> 3 V DC
Maximum permissible voltage30 V DC
Current drawn< 0.1 mA
✕
Do not power the siren from the siren output
The SIR input is a logic input. It draws less than 0.1 mA. Power goes exclusively through DC 12-24. Connecting the power supply to the siren output destroys the output stage on the first trigger: the current drawn in alarm reaches 1.2 A.

Connection depending on the panel

The setting to use depends on one thing only: the electrical behaviour of the panel siren output. The reliable method is to measure it, rather than assume it.

1
Measurement at rest
Panel not in alarm, siren not connected. Measure between the siren output and the common 0 V. Then check with an ohmmeter whether the output is open rather than at 0 V: both read the same on a voltmeter.
2
Measurement in alarm
Trigger an alarm, or force the output from the panel test menu. Note the new value.
3
Working out the setting
Look up the pair of values in the table of the four combinations, then program SIR accordingly.

The table below gives the most common configurations by brand. It is a starting point, not a certainty: the type and polarity of the outputs remain programmable on most panels.

Panel Output used Behaviour SIR setting
Honeywell Galaxy — G2, G3, Dimension, Flex Output 1001, external sirens. Transistor output, open collector switching to 0 V +12 V at rest, 0 V in alarm PO+ / NC — factory setting, nothing to change
Vanderbilt SPC Output programmed as an external siren type Depends on the output type declared in the configuration To be determined by measurement
TIL Technologies — TILLYS, CUBE Command register pointing to an ML module output, for example XA0102 Relay: dry contact. Transistor: switching to 0 V Depending on the module output type
Relay output — any manufacturer Potential-free COM / NC / NO contact Set by the chosen wiring PO+ / NC with COM on +12 V

Dry-contact output

A relay output applies no potential. It is the wiring that builds the logic expected by the input.

To keep the factory setting PO+ / NC: connect the common COM to +12 V, and the normally closed contact of the relay to SIR. At rest, the siren receives +12 V. On activation, the contact opens and the input goes high-impedance, which matches the “0 V or nothing” state of the alarm condition.

!
Galaxy — DIP switch SW3
On Galaxy, DIP SW3 in the OFF position switches the transistor outputs to pure open collector and removes the internal pull-up resistor. The output then no longer presents +12 V at rest, but an open state. The SIR input in PO+ / NC ends up in permanent alarm. Two ways out: leave SW3 in the pulled-up position, or switch the input to PO- / NO.

Programming the SIR menu

The interface consists of three seven-segment displays and four buttons: OK confirms, RETURN goes up one level, + and - scroll through the values.

Programming area of the ATLS THE VOICE EXT siren: seven-segment displays, OK, RETURN, plus and minus buttons, and configuration DIP switches

Click to enlarge

1
Entering programming
Hold OK for 2 seconds. The word MENU scrolls, then SIR appears. Confirm with OK.
2
Polarity
Select PO+ or PO- with + and -. Confirm.
3
Trigger mode
Select NC, normally closed, or NO, normally open. Confirm.
4
Tone
Choose from S01 to S04. On a THE VOICE EXT, the expected value is S02.
5
Strobe
FL0 no strobe, FL1 for the strobe to accompany the tone. The strobe stays on until SIR is reset, even after the sound has stopped.
6
Leaving programming
Press RETURN until the displays go off. It also exits automatically after ten minutes without any action.

Available tones

Code Tone Duration Sound level
S01 Indoor, SI-MAX type 10 min 107 dB — 1.1 A
S02 External NF C 48-265, 1400 to 1600 Hz. THE VOICE EXT default 3 min 107 dB — 1.2 A
S03 SI-MAX no. 2, low consumption. Fault signalling 10 min 100 dB — 0.25 A
S04 Fire NF S 32-001 Continuous until reset 92 dB — 0.6 A

The tone chosen on SIR also sets the follow-up sound applied to the messages of inputs IN1 to IN4, when the siren follow-up parameter is set to SI1.

Reset

There are two reset levels. In both cases: cut the external power supply, disconnect the battery, then reconnect while holding a button down.

Button held Scope
RETURNErases the recorded messages only
OKFull return to factory programming: messages, options and input trigger modes

The characters rotating on the displays confirm that the reset has been taken into account.

Common pitfalls

✕
Tone S01 on an external siren
This is the most frequent mix-up. S01 is the indoor tone, timed at 10 min. On an EXT, the expected value is S02: compliant with NF C 48-265 and timed at 3 min. An EXT left on S01 sounds for ten minutes with a non-compliant tone.
✕
Open collector without a pull-up resistor
In PO+ / NC, the input requires a clean +12 V at rest. Without a pull-up, it stays high-impedance, a state read as an alarm: the siren sounds as soon as it is powered up. Restore the pull-up at the panel, or switch to PO- / NO.
!
0 V not shared
Siren on a remote power supply, with no ground link to the panel: the SIR reference floats. Triggering becomes erratic and false triggers appear on electrical interference.
!
Strobe still on after the sound stops
This is not a fault. With FL1, the strobe stays on until the input is reset (SIR), whereas the sound stops after 3 min. The strobe only goes off after acknowledgement at the panel.
!
DIP 3 forgotten when running without a battery
Without a battery and with DIP 3 OFF, the siren reports a battery fault at the daily test. Set DIP 3 to ON. Check at the same time that the power supply can handle the 2 A drawn in alarm: the battery's energy reserve is no longer there to absorb the peak.
!
Inputs wired on a slave siren
In slave mode, the inputs no longer trigger anything. Connected to 0 V, they block the matching message. Wiring SIR on a slave to mirror the master's trigger has the opposite effect.
!
Bus end-of-line resistor
With several sirens, the end-of-line jumper is only switched on at the master and at the last slave of the bus. Enabled on an intermediate siren, it degrades the RS-485 link and causes audio synchronisation losses.
PO+ / PO- — Input polarity
Defines whether the input reacts to the presence of a positive potential (PO+, threshold > 3 V) or to its absence (PO-, threshold < 2 V).
NC / NO — Trigger mode
On THE VOICE, NC triggers when the rest condition disappears, NO when it appears. Always combine it with the polarity.
NF C 48-265
French standard defining the sound modulation of external intruder alarm sirens: sweep from 1400 to 1600 Hz, duration limited to 3 min.
BLK SIR — Siren blocking
Output switching a +12 V while a voice message is playing, to cut the site's conventional sirens and make the message audible. Insert a relay or a diode to avoid any short circuit with the panel output.
TBTS — Safety extra-low voltage (SELV)
Voltage level defined by EN 60950, applicable to all the terminals of THE VOICE.
SICB
Built-in charging circuit that correctly charges the battery over the whole 10 to 30 V DC range.

Source: ATLS installation manual — THE VOICE-INT / THE VOICE-EXT, reference NOTINS0FR000065 (in French).