FRLire cette fiche en françaisThe Finder 46.61 is a 16 A electromechanical relay with one changeover contact.
In security systems, it is the interface between a panel output, which only supplies a few tens of milliamps, and a hungrier load: siren, strike, maglock, gate or lighting.
It plugs into the 97.01 socket, on a DIN rail, which carries all the terminals. Example used here: part number 46.61.9.012.0040, 12 V DC coil, lockable test button and mechanical indicator.
- Terminals: coil between
A1(+) andA2(−). ChangeoverCOM 11,NO 14,NC 12. - At rest:
COMonNC. Coil energised:COMonNO. - 12 V DC coil: 40 mA, from 8.8 to 13.2 V.
- No built-in diode: add a Finder 99.02 module on the socket.
- Isolation: control and power kept separate, reinforced 6 kV.
What is inside the relay
Two electrically independent parts, and one piece that passes the movement on:
- Control: a coil wound around an iron core.
- Power: a moving contact, the common, and two fixed contacts.
- In between: an armature on a pivot. A spring brings it back to rest as soon as the coil is no longer powered.
The relay in operation
The relay on its socket. The buttons energise the coil, press the test button or start an automatic cycle: you can see the contact change over.
At rest, the spring holds the armature: COM is connected to NC.
11 is connected to NC 12, normally closed: a load on NC is powered.A1 and A2: the magnetised core pulls the armature, which pivots and stretches the spring. The contact leaves NC 12 for NO 14: the load on NO is powered, the one on NC is cut.NC 12.- During changeover: the common is connected to neither contact.
- Voltage spike: a coil is an inductance. At switch-off, it gives back its energy as a reverse voltage spike, up to several hundred volts without protection. Hence the flyback diode, section 6.
Terminal markings of the 97.01 socket
Two markings: the current labels with their number, and an older numbering from 1 to 5. Coil terminals on one side, contact terminals on the other.
| Marking (old no.) | Role |
|---|---|
A1 (5) | Coil, + side |
A2 (1) | Coil, − side |
COM 11 (4) | Contact common |
NO 14 (3) | Closed when the coil is energised |
NC 12 (2) | Closed at rest |
- Solid wire: up to 1 × 6 mm² or 2 × 2.5 mm².
- Flexible wire: up to 1 × 4 mm² or 2 × 2.5 mm².
- Fitting: strip 8 mm, tighten to 0.8 Nm.
Wiring the control side from a panel
- Open-collector output (it switches the 0 V, the most common case):
A1to the permanent +12 V of the panel or power supply,A2to the output. With the output active, the coil circuit closes and the relay pulls in. - Output that delivers +12 V: the output on
A1,A2to 0 V.
On the power side, the contact is dry and has no polarity. NO for a load active on command, NC for a load active at rest, for example a maglock powered as long as the door is locked. Fail-secure or fail-safe: see the guide Fail-secure or fail-safe strike: how it works, wiring and uses.
Specifications to know
The 46.61 with a 12 V DC coil, on the 97.01 socket.
| Parameter | Value |
|---|---|
| Contact | 1 changeover, 16 A, 25 A peak |
| Rated / max voltage | 250 / 440 V AC |
| AC1 / AC15 load (230 V) | 4000 VA / 750 VA |
| DC1 breaking capacity | 12 A at 24 V 0.5 A at 110 V 0.15 A at 220 V |
| 12 V DC coil | 300 Ω, 40 mA, 0.5 W |
| Coil range | 8,8 à 13,2 V |
| Holding / release | 0.4 Un / 0.1 Un |
| Coil / contact isolation | Reinforced, 8 mm, 6 kV, 4000 V AC |
| 97.01 socket | 16 A, 250 V AC, 35 mm rail or panel |
- On DC: the breaking capacity depends heavily on the voltage. Comfortable at 12 or 24 V, it drops sharply above that.
- Inductive DC load (strike, maglock): a reverse diode in parallel with the load gives the contact back the service life it would have on a resistive load. On the other hand, the load switches off more slowly.
Protecting the control side with a diode
The 46.61 has no flyback diode on its coil. Without one, the spike at each switch-off can damage the panel's transistor output. The cleanest option: plug a Finder 99.02 module into the socket, between the coil terminals.
| Part number | Function |
|---|---|
99.02.3.000.00 | Diode only, polarity +A1. 6 to 220 V DC |
99.02.9.024.99 | LED and diode, polarity +A1. 6 to 24 V DC |
Without a module: a 1N4007 diode in reverse, cathode on A1, anode on A2.
The test button of the 0040 version
The suffix 0040 means the version with a lockable test button and mechanical indicator. The button forces the relay into the operated position, to check the load without powering the coil.
- Plastic lug intact (above the button): the contact returns to rest as soon as you let go.
- Lug broken off: pressing and turning locks the contact in the operated position until the button is put back. Quick, firm movement.
Common pitfalls