Skip to content

Finder relay: how it works and how to wire it

17 October 2026 · updated 28 October 2026 · Theo

FRLire cette fiche en français
●○
Difficulty: Beginner
⏱️
Reading time: ~8 min

The Finder 46.61 is a 16 A electromechanical relay with one changeover contact.

In security systems, it is the interface between a panel output, which only supplies a few tens of milliamps, and a hungrier load: siren, strike, maglock, gate or lighting.

It plugs into the 97.01 socket, on a DIN rail, which carries all the terminals. Example used here: part number 46.61.9.012.0040, 12 V DC coil, lockable test button and mechanical indicator.

⚡
The essentials in 30 seconds
  • Terminals: coil between A1 (+) and A2 (−). Changeover COM 11, NO 14, NC 12.
  • At rest: COM on NC. Coil energised: COM on NO.
  • 12 V DC coil: 40 mA, from 8.8 to 13.2 V.
  • No built-in diode: add a Finder 99.02 module on the socket.
  • Isolation: control and power kept separate, reinforced 6 kV.

What is inside the relay

Two electrically independent parts, and one piece that passes the movement on:

  • Control: a coil wound around an iron core.
  • Power: a moving contact, the common, and two fixed contacts.
  • In between: an armature on a pivot. A spring brings it back to rest as soon as the coil is no longer powered.

The relay in operation

The relay on its socket. The buttons energise the coil, press the test button or start an automatic cycle: you can see the contact change over.

Coil0 V
ContactCOM → NC
Active loadNC (12)

At rest, the spring holds the armature: COM is connected to NC.

Finder 46.61.9.012.0040 relay on a 97.01 socket: coil, armature, NC and NO contacts Finder 46.61.9.012.0040, 12 V DC coil 97.01 socket Coil Spring Test NC NO Armature diode A1 A2 COM11 NO14 NC12 +12 V 0 V Panel output +V load NC load NO load 0 V
Current in the coil Magnetic flux Current in the load Diode, at switch-off Wire with no current A1, A2: coil terminals, + and −. 11, 12, 14: common, normally closed (NC) and normally open (NO) contacts.
1
At rest
The spring holds the armature. The common 11 is connected to NC 12, normally closed: a load on NC is powered.
2
Coil energised
12 V between A1 and A2: the magnetised core pulls the armature, which pivots and stretches the spring. The contact leaves NC 12 for NO 14: the load on NO is powered, the one on NC is cut.
3
At switch-off
The field collapses, the spring brings the armature back, the common returns to NC 12.
  • During changeover: the common is connected to neither contact.
  • Voltage spike: a coil is an inductance. At switch-off, it gives back its energy as a reverse voltage spike, up to several hundred volts without protection. Hence the flyback diode, section 6.

Terminal markings of the 97.01 socket

Two markings: the current labels with their number, and an older numbering from 1 to 5. Coil terminals on one side, contact terminals on the other.

Marking (old no.) Role
A1 (5)Coil, + side
A2 (1)Coil, − side
COM 11 (4)Contact common
NO 14 (3)Closed when the coil is energised
NC 12 (2)Closed at rest
  • Solid wire: up to 1 × 6 mm² or 2 × 2.5 mm².
  • Flexible wire: up to 1 × 4 mm² or 2 × 2.5 mm².
  • Fitting: strip 8 mm, tighten to 0.8 Nm.

Wiring the control side from a panel

  • Open-collector output (it switches the 0 V, the most common case): A1 to the permanent +12 V of the panel or power supply, A2 to the output. With the output active, the coil circuit closes and the relay pulls in.
  • Output that delivers +12 V: the output on A1, A2 to 0 V.

On the power side, the contact is dry and has no polarity. NO for a load active on command, NC for a load active at rest, for example a maglock powered as long as the door is locked. Fail-secure or fail-safe: see the guide Fail-secure or fail-safe strike: how it works, wiring and uses.

!
Coil voltage
The 12 V DC coil accepts 8.8 to 13.2 V. A panel power supply set to 13.8 V for battery charging exceeds this maximum. Check the actual voltage at the connection point before wiring the relay directly.

Specifications to know

The 46.61 with a 12 V DC coil, on the 97.01 socket.

Parameter Value
Contact1 changeover, 16 A, 25 A peak
Rated / max voltage250 / 440 V AC
AC1 / AC15 load (230 V)4000 VA / 750 VA
DC1 breaking capacity12 A at 24 V
0.5 A at 110 V
0.15 A at 220 V
12 V DC coil300 Ω, 40 mA, 0.5 W
Coil range8,8 à 13,2 V
Holding / release0.4 Un / 0.1 Un
Coil / contact isolationReinforced, 8 mm, 6 kV, 4000 V AC
97.01 socket16 A, 250 V AC, 35 mm rail or panel
  • On DC: the breaking capacity depends heavily on the voltage. Comfortable at 12 or 24 V, it drops sharply above that.
  • Inductive DC load (strike, maglock): a reverse diode in parallel with the load gives the contact back the service life it would have on a resistive load. On the other hand, the load switches off more slowly.

Protecting the control side with a diode

The 46.61 has no flyback diode on its coil. Without one, the spike at each switch-off can damage the panel's transistor output. The cleanest option: plug a Finder 99.02 module into the socket, between the coil terminals.

Part number Function
99.02.3.000.00Diode only, polarity +A1. 6 to 220 V DC
99.02.9.024.99LED and diode, polarity +A1. 6 to 24 V DC

Without a module: a 1N4007 diode in reverse, cathode on A1, anode on A2.

The test button of the 0040 version

The suffix 0040 means the version with a lockable test button and mechanical indicator. The button forces the relay into the operated position, to check the load without powering the coil.

  • Plastic lug intact (above the button): the contact returns to rest as soon as you let go.
  • Lug broken off: pressing and turning locks the contact in the operated position until the button is put back. Quick, firm movement.
!
Button left locked
It keeps the load active, whatever the state of the control output. Check it at the end of the job.

Common pitfalls

✕
A1 and A2 swapped with a diode module
With a 99.02 of polarity +A1, the diode conducts forward: the control output is short-circuited through it.
!
No flyback diode
The relay works, but each switch-off sends a spike to the output. The fault often shows up after several months: a destroyed output.
!
Power supply at 13.8 V
Maximum of the 12 V DC coil: 13.2 V. Set higher for battery charging, the power supply goes outside the relay's range.
!
NO and NC mixed up
A maglock on NO instead of NC stays unpowered at rest: the door is no longer locked. Think in terms of the output state at rest.

Finder documentation: series 46 datasheet (46.61 relay, 97.01 socket, 99.02 modules; French edition).

Glossary
Changeover contact
Contact with three terminals, common, NO and NC, whose common switches from one to the other depending on the coil state.
Flyback diode
Diode fitted in reverse across a coil to absorb the voltage spike produced at switch-off.
Open collector
Transistor output that switches the 0 V to the load, the + being supplied separately.
DC1
Utilisation category for resistive DC loads, used to express the breaking capacity of a contact.