Fail-secure or fail-safe strike: how it works, wiring and uses

18 October 2026 · updated 28 October 2026 · Theo

FRLire cette fiche en français
●○
Difficulty: Beginner
⏱️
Reading time: ~7 min

An electric strike replaces the mechanical strike plate in the door frame. Depending on whether it is powered or not, it holds or releases the latch bolt of the lock.

Two families work the opposite way round. Fail-secure (power to open, “à émission” in French): it releases when powered. Fail-safe (power to lock, “à rupture”): it releases when the power is cut.

The choice decides what happens to the door during a power cut. Principles, wiring, uses and emergency exit rules below.

⚡
The essentials in 30 seconds
  • Fail-secure: locked when unpowered, released when powered. During a power cut, the door stays closed.
  • Fail-safe: locked when powered, released when the power is cut. During a power cut, the door opens.
  • Control: fail-secure on the NO contact, fail-safe on the NC.
  • Consumption: a fail-safe strike draws current all the time. Size the power supply and batteries accordingly.
  • Emergency exit: in France, only a fail-safe device certified to NF S 61-937 is allowed.

What an electric strike does

In a standard door, the latch bolt sits in the strike plate fixed to the frame. To open, you turn the handle or the key to pull the latch back.

An electric strike has a moving keeper, held or released by a catch driven by a coil. With the keeper free, it pivots under the push of the latch: the door opens without touching the lock.

Fail-secure or fail-safe

The fail-secure strike

  • At rest: coil not powered, the catch blocks the keeper. Door closed.
  • To open: the control applies the voltage, the coil pulls the catch back, the door can be pushed.
  • Consumption: only while opening, often a few seconds.
  • Power cut: it stays locked. Nobody can get in from outside, but the inside handle still lets people out.
  • Use: a door that must stay closed whatever happens, for example a plant room or a store room.

The fail-safe strike

  • At rest: coil powered all the time, it holds the catch.
  • To open: the control cuts the power, the strike releases.
  • Power cut: it releases too. Fail-safe principle: any loss of power, including a cut cable, opens the way.
  • Consumption: permanent, day and night. Count it in the power supply and the battery backup time.

Simulator

Choose the strike type, then activate the control or cut the power. “Push the door” shows whether the latch can get past the strike.

CoilUnpowered
StrikeLocked
DoorClosed

At rest, the fail-secure strike is not powered: it stays locked without drawing current.

Electric strike: power supply, control contact, coil, catch and door seen from above Strike Power supply 12 V Control (NO) Door
Current in the coil Wire with no current Catch engaged Catch released Cross: power cut

Comparison

Criterion Fail-secure / Fail-safe
At restFail-secure: unpowered, locked
Fail-safe: powered, locked
To openFail-secure: apply power
Fail-safe: cut power
Power cutFail-secure: stays locked
Fail-safe: releases
Cable cutFail-secure: stays locked
Fail-safe: releases
ConsumptionFail-secure: only while opening
Fail-safe: permanent
Control contactFail-secure: NO
Fail-safe: NC
Typical useFail-secure: room to protect
Fail-safe: passage that must release

Wiring the control

The strike is most often driven by the relay output of a door controller or a standalone reader.

  • Fail-secure: NO contact. It closes during the release time and powers the strike.
  • Fail-safe: NC contact. It powers the strike at rest and opens during the release time to release it.

On DC, protect the coil with a flyback diode or a varistor. Many strikes have one built in. Otherwise, the spike at each switch-off ends up damaging the control contact.

⚡
Reversible strikes and options
Many models can be set to fail-secure or fail-safe, by jumper or by a part to turn round depending on the manufacturer. Some fail-secure strikes have a memory: they stay released after the command until the door is opened.

Emergency exits

A door on an escape route must be able to open in all circumstances. A fail-secure strike on its own is not allowed there: it stays locked during a power cut.

  • The device: under French rules, a safety-actuated device (DAS) certified to NF S 61-937, working on power cut. Locked in standby position, unlocked in safety position.
  • Its control: a manual call point with a switch function near the exit, inserted on the device's remote control line. Or an emergency exit control device compliant with NF S 61-934.
!
A fail-safe strike is not enough
Not all of them are certified to NF S 61-937. Check the test report of the complete device, follow the manufacturer's wiring diagram and the building regulations.

Common pitfalls

✕
Fail-secure on an emergency exit
During a power cut, the door stays locked: the exit is no longer guaranteed. A certified fail-safe device is required.
!
NO and NC swapped
A fail-safe strike on NO is free at rest and locks during the command: door open all the time, locked when a badge is presented.
!
Undersized power supply
A fail-safe strike draws current day and night. Several on the same power supply quickly drain the battery during a mains failure, and all the doors release.
!
Door under pressure
Seal too tight, badly adjusted door closer, someone pushing before the command: the latch presses on the keeper. Some strikes no longer release under this preload. Check the value allowed by the manufacturer and adjust the door.

Regulations (France): article CO 46 of the French fire safety rules for public buildings (ERP) (locking of emergency exit doors).

Glossary
Latch bolt
Bevelled bolt of the lock, pulled back by the handle, which sits in the strike when the door closes.
Strike keeper
Moving part of the electric strike that pivots to let the latch through when the catch is released.
Fail-safe principle
Principle whereby a loss of power puts the device in its safe position, here door unlocked.
DAS
Safety-actuated device (“Dispositif actionné de sécurité” in French rules). Locking an emergency exit falls into this category and is covered by NF S 61-937.