Cable voltage drop
What actually reaches the end of the cable: the line loss, the voltage at the device terminals, and how far you can go with that cross-section.
Voltage at the far end
–
Enter the length and the current.
- Line loss
- –
- Maximum length with this cable
- –
- Minimum cross-section for this length
- –
How it is calculated
The starting point is the rule of thumb from the Harmonia manual: 100 m of 0.5 mm² cable (0.8 mm conductor) carrying 100 mA loses 1 V. The loss grows with length and current, and falls when the cross-section increases or when you double the power pairs.
- Loss = 1 V × (length ÷ 100 m) × (current ÷ 100 mA) × (0.5 mm² ÷ cross-section) ÷ pairs
- Voltage at the far end = starting voltage − loss
The rule rounds to the volt: it is an estimate. At commissioning, measure the voltage at the device terminals.
If the voltage is too low
- Double the power pairs, or increase the cable cross-section.
- Add a power supply close to the distant devices.
- Or combine both.