Cable voltage drop

What actually reaches the end of the cable: the line loss, the voltage at the device terminals, and how far you can go with that cross-section.

1Cable
mm²
Power pairs
m

From the power supply to the device.

2Current
mA

All the devices powered by this cable, according to their manuals.

3Voltages
V

13.8 V: typical voltage of a 12 V power supply output (Aritech ATS1201E).

Device minimum voltage
V

The value is in the device manual.

Voltage at the far end

–

Enter the length and the current.

Line loss
–
Maximum length with this cable
–
Minimum cross-section for this length
–

How it is calculated

The starting point is the rule of thumb from the Harmonia manual: 100 m of 0.5 mm² cable (0.8 mm conductor) carrying 100 mA loses 1 V. The loss grows with length and current, and falls when the cross-section increases or when you double the power pairs.

  • Loss = 1 V × (length ÷ 100 m) × (current ÷ 100 mA) × (0.5 mm² ÷ cross-section) ÷ pairs
  • Voltage at the far end = starting voltage − loss

The rule rounds to the volt: it is an estimate. At commissioning, measure the voltage at the device terminals.

If the voltage is too low

  • Double the power pairs, or increase the cable cross-section.
  • Add a power supply close to the distant devices.
  • Or combine both.

Sources: Harmonia 2650 / 2660 / 2680 (French manual), line loss · SATEL INTEGRA Plus (French manual), keypad bus connection · Aritech ATS1201E (French manual), specifications