Skip to content

Battery life

How long the battery keeps the control panel and its devices running when mains power fails, and what capacity to plan for the required time.

1Standby current

Everything the battery powers. The easiest way: one typical device per button, one more with each tap. For an exact value, search for the precise model.

Quick add

45 devices, values taken from the manuals. See the catalogue

mA

Total 0 mA

2Battery
Ah
Number of batteries
3Required standby time
h

Estimated backup time

–

Enter at least one consumption.

Minimum capacity for 36 h
–
Maximum current for 17 Ah over 36 h
401 mA

How it is calculated

Only 85% of the battery capacity is counted: that is the usable power Vanderbilt uses for SPC control panels.

  • Backup time = 0.85 × capacity (Ah) ÷ consumption (A)
  • Minimum capacity = consumption (A) × time (h) ÷ 0.85
  • Maximum current = 0.85 × capacity (Ah) ÷ time (h)

Two batteries count as the sum of their capacities. If the consumption exceeds what the power supply can deliver, you need an expander with its own power supply.

Standby and recharge times

RequirementStandbyRecharge time
EN 50131 grade 212 h72 h
INCERT24 h24 h
EN 50131 grade 3, VdS-B30 h24 h
NF&A2P grade 2 (EN + PSTN)36 h72 h
NF&A2P grade 3 (EN + PSTN), VdS-C60 h24 h

The current consumption catalogue

45 devices, each with the document its standby current comes from. A device is missing? Suggest it, with its manual.

Sources: SPC 3.11 (French manual), calculating the power required for the battery · Aritech ATSx500A (French manual), auxiliary current and battery capacity · SATEL INTEGRA Plus (French manual), current consumption